Features
|
|
Low OPEX: | Best in class fuel efficiency with O2E technology |
Robust and Reliable Product: | Lowest maintenance and trouble free product with Kirloskar Engines |
Option of Air Cooled and Water Cooled Engines | |
Compliance: | Latest Government Emission Norms CPCB II |
Start Type: | Controller Based Easy Push Start Type |
Customer Service: | Quick and affordable door step service coverage (420+ service touch points and 6000+ KOEL trained service professionals on field) |
Warranty: | 2 years warranty & labour free onsite service under warranty period |
Product Specifications
Prime Rating at rated rpm ( as per ISO8528)1 |
kVA |
40 |
40 |
45 |
62.5 |
62.5 |
82.5 |
100 |
125 |
125HD |
||||
kW |
32 |
32 |
36 |
50 |
50 |
60 |
80 |
100 |
100 |
|||||
Genset Model |
|
KG1-40AS |
KG1-40WS |
KG1-45WS |
KG1-62.5AS |
KG1-62.5AS |
KG1-82.5WS |
KG1-100WS |
KG1-125WS |
KG1-125WS HD |
||||
Frequency |
Hz |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
50 |
||||
Power factor |
lagging |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
0.8 |
||||
Voltage |
V |
230(1Ø) & 415(3Ø) |
415(3Ø) |
|||||||||||
Governing class (As per ISO 8528 Part-V) |
|
G2 |
G2 |
G2 |
G2 |
G2 |
G2 |
G3 |
G3 |
G3 |
||||
Noise level |
dBA |
< 75 |
< 75 |
< 75 |
< 75 |
< 75 |
< 75 |
< 75 |
< 75 |
< 75 |
||||
Fuel Consumption* |
At 100% Load |
Ltrs/hr |
9.9 |
9.2 |
10.3 |
16.2 |
14.1 |
18.8 |
21.9 |
27.4 |
27.5 |
|||
At 75% Load |
7.9 |
7.4 |
8.7 |
12.7 |
11.3 |
13.8 |
16.9 |
20.2 |
21.4 |
|||||
At 50% Load |
5.8 |
5.5 |
5.9 |
8.9 |
7.5 |
9.9 |
12.2 |
15.3 |
15.3 |
|||||
Fuel tank capacity |
Ltrs |
100 |
100 |
100 |
150 |
150 |
230 |
230 |
230 |
50 |
||||
Weight of genset with canopy (approx..)^ |
Dry |
Kg |
1270 |
1250 |
1250 |
1700 |
1420 |
1710 |
2040 |
2090 |
2520 |
|||
Wet |
Kg |
1370 |
1335 |
1335 |
1825 |
1550 |
1840 |
2240 |
2290 |
2730 |
||||
Overall dimensions of genset^ |
Length |
mm |
2400 |
2550 |
2550 |
3150 |
2800 |
3200 |
3220 |
3220 |
3650 |
|||
Width |
mm |
1050 |
1050 |
1050 |
1200 |
1100 |
1100 |
1300 |
1300 |
1350 |
||||
Height |
mm |
1670 |
1450 |
1450 |
1635 |
1595 |
1595 |
1795 |
1795 |
1915 |
||||
Electrical Battery starting voltage |
Volts-DC |
12 |
12 |
12 |
12 |
12 |
12 |
12 |
12 |
12 |
||||
ENGINE | ||||||||||||||
Engine Model |
|
HA494TCI G1 |
3R1040TA G1 |
3R1040TA G1 |
HA694TCI G1 |
4R810TA G1 |
4R810TA G1 |
4K1080TA G2 |
4K1080TA G2 |
6R1080TA G1 |
||||
Rated output (Prime Continuous rating as per ISO 8528-1) |
KW |
41.19 |
41.2 |
41.2 |
61 |
61 |
74.8 |
114.7 |
114.7 |
114.7 |
||||
HP |
56 |
56 |
56 |
83 |
83 |
102 |
156 |
156 |
175 |
|||||
No. of cylinder |
Number |
4 |
3 |
3 |
6 |
4 |
4 |
4 |
4 |
6 |
||||
Cubic capacity |
Ltrs |
3.77 |
3.12 |
3.12 |
5.65 |
3.24 |
4.16 |
4.32 |
4.32 |
6.49 |
||||
Bore x Stroke |
mm |
100 x 120 |
105 x 120 |
105 x 120 |
105 x 120 |
100 x 120 |
96 x 112 |
105 x 120 |
105 x 125 |
105 x 125 |
||||
Rated Speed |
RPM |
1500 |
1500 |
1500 |
1500 |
1500 |
1500 |
1500 |
1500 |
1500 |
||||
Aspiration |
NA/TC/TA |
TC |
TA |
TA |
TC |
TA |
TA |
TA |
TA |
TC |
||||
Lube Oil change period |
Hrs |
500 |
500 |
500 |
500 |
500 |
500 |
500 |
500 |
500 |
||||
Lube Oil Sump Capacity |
Ltrs |
8.3 |
8 |
8 |
11 |
10 |
10 |
14 |
14 |
18 |
||||
Coolant Capacity |
Ltrs |
11.5 |
11.5 |
117.5 |
24 |
21 |
21 |
28 |
||||||
ALTERNATOR |
||||||||||||||
Insulation Class |
|
Class H |
||||||||||||
Alternator Efficiency (at 100% load) 0.8 pf** |
% |
89.2 |
89.2 |
89.2 |
91 |
91 |
91.4 |
92 |
92.5 |
92.5 |
||||
Alternator Efficiency (at 75% load) 0.8 pf** |
Sec |
< 20% |
< 16% |
< 16% |
< 20% |
< 20% |
< 20% |
< 20% |
< 20% |
< 20% |
||||
Max Time to build up rated voltage at Rated RPM |
< 5 sec provided engine reach the rated speed |
< Voltage recovery time 6 sce |
||||||||||||